Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit
The discharge temperature thermistor (TH4) circuit is detected as either open (temperature reading 37°F [3°C] or less) or short (temperature reading 422°F [217°C] or more) during compressor operation. This fault prevents accurate monitoring of compressor discharge temperature, impacting system protection and control. Detection is inoperative for the first 10 minutes of compressor start-up and during/after defrosting.
Click steps to track your progress.
Check the connection of the TH4 connector on the outdoor controller circuit board for proper seating.
Check the lead wire for thermistor TH4 for any breaks or damage.
Measure the resistance value of thermistor TH4 and compare it to expected values for the measured temperature.
If TH4 and its wiring are confirmed correct, replace the outdoor controller circuit board.