Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit
An overcurrent condition on the DC bus or compressor is detected within 30 seconds after the compressor starts operating. This indicates a locked compressor state. Common causes include a closed stop valve, decreased power supply voltage, loose, disconnected, or reversed compressor wiring connection, a defective compressor, or a faulty outdoor power board.
Click steps to track your progress.
Open the stop valve.
Check the facility of the power supply.
Correct the U·V·W phase wiring to the compressor. Refer to section 10-9 (Outdoor power circuit board).
Check the compressor. Refer to section 10-6.
Replace the outdoor power circuit board.