Mitsubishi Electric · R410A Systems
The outdoor unit's heat exchanger sensor (ThOR) is defective (open or short circuit) or has a poor connection to the outdoor unit PCB. This can also indicate excessively high cooling pressure, compromising system efficiency and safety.
Click steps to track your progress.
Measure the resistance of the ThOR sensor at its leads — compare to a resistance-temperature chart if available.
Inspect the ThOR sensor's connector on the outdoor unit PCB — verify it is securely seated.
Measure system high-side pressure using manifold gauges during cooling operation.
Verify condenser coil cleanliness and airflow if high pressure is observed.