EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. R410A Systems
  4. E37-5
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

E37-5

Outdoor Heat Exchanger Thermistor 5 Failure (Tho-R5)

Mitsubishi Electric · R410A Systems

What does E37-5 mean?

The fifth outdoor heat exchanger thermistor (Tho-R5) is defective. This prevents accurate temperature measurement of a specific section of the outdoor coil, impacting system control and protection.

Common Causes

  • Outdoor heat exchanger thermistor 5 (Tho-R5) has failed.
  • Wiring to Tho-R5 is broken or shorted.
  • Tho-R5 reading is out of specified limits.
  • Defective Tho-R5 thermistor.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure the resistance of thermistor Tho-R5 at its leads — compare to a resistance-temperature chart if available.

  2. 2

    Inspect the connector for Tho-R5 on the outdoor unit PCB — verify it is securely seated and free from corrosion.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

E0Transmitting/Receiving Signal ErrorE112Auto Addressing Conflict / Factory Address Setting ErrorE14Master/Slave System Configuration Error
Source: Mitsubishi Electric R410A Systems
Open Manual (Page 4)Search more codes in this manual