Mitsubishi Electric · R410A Systems
The outdoor unit has detected an open circuit in the L3 phase of the main power supply. This indicates a loss of one of the three input phases, potentially leading to unbalanced operation or motor damage.
Click steps to track your progress.
Measure voltage between L1-L2, L2-L3, and L3-L1 at the outdoor unit main power terminals — expect balanced 3-phase voltage.
Inspect all wiring connections for the L3 phase at the outdoor unit's main power terminals for looseness or corrosion.
Check the integrity of the circuit breaker or fuse protecting the L3 phase in the electrical panel.