P1

Intake Air Sensor Abnormal

Mitsubishi Electric · R410A Systems

What does P1 mean?

The intake air sensor (room temperature sensor) on the indoor unit is abnormal, indicating an open circuit, short circuit, or incorrect resistance. This impacts the system's ability to accurately sense room temperature and control operation.

Common Causes

  • Intake air sensor (20) is abnormal.
  • Faulty intake air temperature/pressure sensor.
  • Wiring issue to the intake air sensor.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure the resistance of the intake air sensor at its leads — compare to a resistance-temperature chart if available.

  2. 2

    Inspect the sensor's wiring and connector on the indoor unit PCB for damage, corrosion, or secure seating.

  3. 3

    Verify the sensor is not physically damaged or dislodged from its intended position.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026