Mitsubishi Electric · R410A Systems
The compressor drew excessive current either during startup (locked rotor during start-up) or during ongoing operation (operating locked). Both conditions indicate a severe mechanical failure or an electrical issue preventing the compressor motor from rotating freely.
Click steps to track your progress.
Measure compressor running current on all three phases using a clamp meter — observe if it spikes before tripping.
Measure winding resistance of the compressor motor phases (U-V, V-W, U-W) and to ground using an ohmmeter.
Verify correct voltage supply to the compressor terminals during startup attempt.
If applicable, check the start capacitor value and Equivalent Series Resistance (ESR) using a capacitor meter.