0x0400 to 0x040F

CPU Bus Unit Setting Error

Omron · CJ-series CJ2 CPU Unit

What does 0x0400 to 0x040F mean?

An installed CPU Bus Unit does not match the CPU Bus Unit registered in the I/O tables. This error indicates a mismatch between the physical hardware and the configured settings. Flag A402.03 and Auxiliary Area A427 indicate the error and the problem unit number respectively.

Common Causes

  • Installed CPU Bus Unit does not match the registered I/O table entry.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Change the registered I/O table using CX-Programmer to match the physically installed CPU Bus Unit.

Browse all codes in this manual (34)