0x80C0 to 0x80C7, 0x80CE, or 0x80CF

I/O Bus Error

Omron · CJ-series CJ2 CPU Unit

What does 0x80C0 to 0x80C7, 0x80CE, or 0x80CF mean?

An error has occurred in the communication bus line between the CPU and I/O Units, or the End Cover is not correctly connected to the CPU Rack or an Expansion Rack. This is a fatal error, indicated by flag A401.14. Auxiliary Area A404 contains the error slot number (00 to 09, with '0F hex' for undetermined slot, '0B hex' for built-in EtherNet/IP port bus error) and rack number (00 to 03, with '0E hex' for missing End Cover).

Common Causes

  • Fault in the bus line cable between the CPU and I/O Units or between Racks.
  • End Cover is not connected to the CPU Rack or an Expansion Rack.
  • Damage to the I/O bus cable or the I/O Units themselves.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Cycle power OFF and ON again to the PLC system.

  2. 2

    If the error persists, turn power OFF and physically check all cable connections between I/O Units and Racks, and verify End Covers are securely connected.

  3. 3

    Inspect I/O bus cables and I/O Units for any signs of physical damage.

  4. 4

    Cycle power OFF and ON again to the Rack's power supply.