Omron · CJ-series CJ2 CPU Unit
A fatal error has occurred in the CPU's memory, indicated by A401.15. A bit in A403 will turn ON to show the location of the error, such as checksum errors in user program memory, PLC Setup, registered I/O tables, routing tables, or CPU Bus Unit Setup. This can be caused by power interruptions during data storage or corrupted settings, preventing the PLC from operating correctly.
Click steps to track your progress.
If A403.00 is ON: Transfer the program again.
If A403.04 is ON: Clear the entire PLC Setup to 0000 and reenter all settings.
If A403.05 is ON: Initialize the registered I/O table and generate a new I/O table.
If A403.07 is ON: Initialize the routing tables and reenter the tables.
If A403.08 is ON: Initialize the CPU Bus Unit setup and reenter the settings.