Omron · CS/CJ Series EtherNet/IP Driver
The system failed to match tags during an operation. This issue indicates a discrepancy in tag definitions or configurations between the system and the external device, preventing correct data association. The number of tags that failed in matching is indicated.
Click steps to track your progress.
Inspect Omron PLC EtherNet/IP I/O Table or Tag Data Link settings in the programming software (e.g., CX-Programmer/Sysmac Studio), verifying data types, sizes, and order of defined tags for the external device.
Inspect external device's EtherNet/IP communication configuration, confirming its tag names, data types, and sizes precisely match the Omron PLC's defined tags and expected data structure.
Compare EtherNet/IP Assembly Instance and Connection Point configurations, including their respective input/output sizes and directions, between the Omron PLC and the external device for any discrepancies.
Verify the correct Electronic Data Sheet (EDS) file for the external EtherNet/IP device is loaded and properly configured within the Omron PLC's EtherNet/IP settings, if applicable, to ensure accurate device profile matching.