Omron · MX2 Series Type V2 Compact Inverter
This overcurrent fault occurs due to conditions not directly tied to constant speed, acceleration, or deceleration, often observed during startup or when the motor is operating at 0 Hz with DC injection braking. It means the inverter's protection circuit was activated unexpectedly, typically around 200% of the rated output current, due to various external or tuning factors.
Click steps to track your progress.
Disconnect the motor from inverter output terminals (U, V, W) and re-apply power; if the fault clears, the issue is with the motor or cable.
Perform an insulation resistance test (megohmmeter) on the motor windings (phase-to-phase and phase-to-ground) to detect shorts.
Visually inspect inverter output cables for physical damage, pinching, or signs of insulation breakdown.
If DC injection braking is used, verify parameters (P1-10 DC braking current, P1-11 DC braking time) are set correctly and within limits for the motor.
Check for proper grounding of the inverter chassis (ground terminal) and shielding of control wiring to mitigate EMI.