Omron · MX2 Series Type V2 Compact Inverter
This error occurs when the usage rate of the regenerative braking circuit exceeds the configured limit (b090), indicating that the braking resistor is being overstressed. This usually happens during frequent or prolonged deceleration cycles, or if the braking resistor's capacity is insufficient for the application's regenerative energy requirements, risking component damage.
Click steps to track your progress.
Monitor the braking resistor usage rate (d005) or regeneration power (d002) to understand the frequency and magnitude of braking events.
Verify the resistance value of the braking resistor (measured with an ohmmeter) matches the inverter's specified range and parameter b091.
Increase the deceleration time parameter (P1-05) to reduce the peak regenerative power and spread out energy dissipation.
Inspect the braking resistor for physical damage, discolored wiring, or signs of excessive heat (charring) and verify its power rating.
Review and adjust the braking resistor usage rate parameter (b090) if the resistor is adequately sized but the default setting is too conservative.