Omron · MX2 Series Type V2 Compact Inverter
This fault indicates a malfunction within the inverter's current detection circuit. This is a critical internal hardware error, as the inverter relies on accurate current feedback for proper motor control and protection. If this error occurs, the inverter is typically faulty and unable to operate correctly, requiring internal repair or replacement.
Click steps to track your progress.
Cycle power to the inverter (main disconnect) for at least 30 seconds; some transient errors can clear with a full power reset.
Disconnect the motor from inverter output terminals (U, V, W) and re-apply power; if the fault persists, it indicates an internal inverter issue.
Visually inspect the inverter's control board and power board for signs of physical damage, burn marks, or discolored components.
Ensure proper grounding of the inverter chassis (ground terminal) and shielding of control wiring to mitigate EMI.
If the fault occurs immediately on power-up without a motor connected, an internal hardware failure of the current detection circuit is highly probable, requiring service.