Omron · MX2 Series Type V2 Compact Inverter
An emergency shutoff fault is triggered when the safety input terminals GS1/GS2 are activated, initiating a protective shutdown of the inverter. This is a critical safety response, indicating that an external emergency stop device or safety system has detected a hazardous condition and commanded the inverter to cease operation immediately.
Click steps to track your progress.
Identify and inspect all external safety devices connected to the GS1/GS2 safety input terminals. Confirm their current state (e.g., E-stop released, gate closed).
Measure the voltage/continuity across the GS1/GS2 terminals at the inverter input, verifying the safety circuit's integrity according to the inverter's safety manual (e.g., 24VDC high for safety active).
Disconnect all external wiring from GS1/GS2. If the fault clears, the issue is with the external safety circuit or its wiring.
Verify parameter A1-01 (Safety Input Configuration) matches the actual external safety circuit wiring (e.g., 1-channel or 2-channel input, NC/NO contacts).
If the fault persists with external wiring disconnected and parameters are correct, the internal safety circuit or control board may be defective and require replacement.