This error occurs when communication is lost or interrupted between the inverter and the remote Digital Operator (Model: 3G3AX-OP01) for a specified duration (e.g., 5 seconds or longer). This indicates a problem with the connection cable or a fault in the Digital Operator itself, preventing the inverter from receiving commands or displaying status.
Click steps to track your progress.
Disconnect and firmly re-connect the communication cable at both the inverter's digital operator port and the remote operator unit. Ensure the latch mechanism engages.
Inspect the communication cable (e.g., RJ45) for any visible damage, kinks, or bent pins. Replace with a known good, shielded cable if damage is suspected.
Power cycle the inverter by removing and reapplying control power for at least 10 seconds to reset the communication interface.
Check parameter C070 (Digital Operator Comm. Timeout) and C071 (Digital Operator Comm. Error Action) to ensure settings are appropriate for the application.
Temporarily connect a local digital operator (if available) directly to the inverter's front panel to determine if the inverter's communication port itself is functional.