Omron · MX2 Series Type V2 Compact Inverter
This fault occurs when a communication timeout is detected between the inverter and its mounted option unit. This typically signifies a disconnection or a communication fault in the option unit, preventing data exchange. The inverter trips to indicate the loss of communication with the critical peripheral.
Click steps to track your progress.
1. Power off the inverter and visually inspect the option unit's communication connector for bent pins or corrosion.
2. Verify communication parameters in the inverter: confirm P7-01 matches the option unit protocol and P7-02 is unique.
3. Measure the voltage supplied to the option unit (e.g., 24VDC) at the inverter's designated terminals or option unit supply pins.
4. Replace the communication cable between the inverter and the option unit (e.g., shielded CAT5e cable).
5. As a diagnostic, temporarily remove the option unit and re-insert it, ensuring it is seated correctly and securely.
6. Test with a known-good, compatible option unit to isolate if the issue is with the unit or the inverter.