Omron · MX2 Series Type V2 Compact Inverter
An overspeed error occurs when the motor's rotation speed, as detected by the encoder, exceeds the configured 'Overspeed Error Detection Level' (P026) multiplied by the maximum frequency. This can be caused by an incorrect P026 setting, improper encoder wiring, or actual runaway motor conditions. The inverter trips to prevent mechanical damage or unsafe operation.
Click steps to track your progress.
1. Monitor the inverter's actual output frequency (e.g., through display parameter d001) and the speed command source (e.g., analog input voltage).
2. Review and adjust parameter P026 (Overspeed Error Detection Level) to ensure it provides a safe margin above maximum operating speed.
3. Use an oscilloscope to check the encoder A/B phase signals for noise or intermittent drops that could cause erroneous speed readings.
4. Check the motor and driven machinery for any mechanical issues that could cause sudden speed increases (e.g., broken coupling, loss of load).
5. Verify parameters P003 (Rated Motor Frequency) and P004 (Maximum Output Frequency) match the motor and application specifications.
6. Temporarily reduce the maximum speed command source or maximum frequency (P004) to test if the overspeed threshold is still triggered.