10260000 hex

Trace Setting Transfer Failure

Omron · NX-series CPU Unit

What does 10260000 hex mean?

The power supply was interrupted while transferring the trace settings in the PLC Function Module. This error is detected at power ON or Controller reset, categorized as an observation level error. User program execution continues, but all trace settings are initialized.

Common Causes

  • The power supply was interrupted while transferring the trace settings.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Transfer the trace settings again.

  2. 2

    Cycle the power supply to the Controller or reset the Controller.

  3. 3

    Ensure the power supply is not interrupted while transferring trace settings.

Browse all codes in this manual (17)