002

Frequency Lower Limit Exceeded

Omron · MX2 Inverter

What does 002 mean?

This warning indicates that the parameter set for the frequency lower limit (A062) is configured to a value higher than the inverter's maximum allowed frequency (A004). This inconsistent setting creates a logical conflict in the drive's operational range.

Common Causes

  • Erroneous manual entry of A062 (Frequency Lower Limit) to a value exceeding the drive's absolute maximum frequency (A004).
  • Parameter configuration error where A062 was mistakenly set to the same value as A004, or even higher.
  • Restoration of an incorrect parameter file that contains an illogical setting for A062.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Access parameter A062 (Frequency Lower Limit) and compare its value to A004 (Inverter Max Allowed Frequency) and A061 (Frequency Upper Limit).

  2. 2

    Set A062 (Frequency Lower Limit) to a value less than or equal to A061 (Frequency Upper Limit) and also less than or equal to A004 (Inverter Max Allowed Frequency). A common starting point is 0 Hz or a very low value.

  3. 3

    Verify the motor's minimum operating frequency requirements for the application and configure A062 accordingly, ensuring it does not exceed A061.

  4. 4

    Save the parameter changes and power cycle the drive. Then re-check the value of A062 to ensure it has been correctly stored.

Browse all codes in this manual (60)