Modbus Exception: Data Out of Range (Holding Register Write)
Omron · MX2 Series Type V2 Compact Inverter
What does 21 hex mean?
This Modbus exception occurs specifically when writing to a holding register if the data value is outside the parameter's permissible range. It's a more specific version of 'Illegal Data Value' (03 hex) for write operations to holding registers. The inverter rejects the write to prevent parameters from being set to an invalid state.
Common Causes
- Attempting to write a value exceeding the maximum or falling below the minimum allowed for a specific holding register (e.g., setting P1-01 (Accel Time) to 0.05s when min is 0.1s).
- The value being written requires specific units or scaling that is not correctly applied by the Modbus master (e.g., voltage in mV but sent in V).
- Parameter is dependent on other settings, and the new value, while seemingly valid, creates an invalid combination with other parameters.
- User input on the Modbus master (e.g., HMI) allows entering values beyond the inverter's limits without validation.
- Race condition or timing issue where another process changes a related parameter, making the attempted write invalid.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Examine the inverter's manual for the specific parameter corresponding to the holding register, noting its minimum, maximum, and default values.
- 2
2. Review the Modbus master's programming logic to ensure the value being written is clamped or validated against the inverter's parameter limits.
- 3
3. Use a Modbus sniffer to verify the exact value transmitted by the master for the holding register in question.
- 4
4. Check if the parameter requires specific conditions (e.g., inverter stopped, motor type selected) before a particular value can be accepted.
- 5
5. Confirm that any scaling factors or unit conversions (e.g., 0.1s represented as 1 in the register) are correctly applied by the master.
- 6
6. Test writing boundary values (e.g., min-1, min, max, max+1) to the register to pinpoint the exact range violation.