Temperature Sensor Malfunction
Omron · SXF Inverter
What does PF Temp Err mean?
This fault indicates a malfunction in one of the drive's internal temperature sensors. Without accurate temperature feedback, the VSD cannot properly protect itself from overheating, which is a critical safety mechanism. This can lead to unmonitored temperature increases and subsequent component failure or damage if the drive continues to operate.
Common Causes
- Open circuit or short circuit in the temperature sensor wiring or connection.
- Failed temperature sensor (e.g., NTC thermistor, PT100/1000) itself.
- Damaged Analogue-to-Digital Converter (ADC) input on the control board for the sensor.
- Loose connector for the temperature sensor on the control board.
- Electromagnetic interference affecting the low-voltage sensor signal.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Power down and disconnect drive. Locate the internal temperature sensor(s) (e.g., on heatsink or power board).
- 2
Measure resistance of the temperature sensor (e.g., NTC thermistor) at ambient temperature and compare to its datasheet value.
- 3
Inspect sensor wiring for cuts, pinches, or loose connections to the control board.
- 4
Reseat the temperature sensor connector on the control board.
- 5
Check for proper shielding of sensor wires if they run near power cables.