Desat

Failure in Output Stage (IGBT Desaturation)

Omron · SXF Inverter

What does Desat mean?

This fault indicates a desaturation of IGBTs in the output stage, signaling a hard short circuit between phases or phase to earth, or an earth fault. It can also be related to the brake IGBT (up to SX-D4037). If left unresolved, it can lead to severe damage to the drive's power components and connected motor, requiring costly repairs.

Common Causes

  • Motor phase-to-phase short circuit due to insulation degradation or mechanical damage.
  • Motor phase-to-earth short circuit in winding or terminal box.
  • Output cable (motor cable) insulation breakdown, shorting phases or phase to earth.
  • Brake IGBT short circuit or faulty gate drive if the drive includes an integrated brake chopper (e.g., SX series).
  • Damaged drive output IGBT module (internal hardware fault).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect motor cables from drive output terminals U, V, W.

  2. 2

    Measure insulation resistance between motor phases (U-V, V-W, W-U) and each phase to ground using a megohmmeter (1000V DC). Expect > 5 MOhms.

  3. 3

    Measure continuity between motor phases and phase-to-ground using a multimeter. Expect open circuit phase-to-ground, low resistance phase-to-phase.

  4. 4

    Inspect motor output cable for visible damage, crushed sections, or water ingress.

  5. 5

    If drive includes a brake chopper, verify the brake resistor and its cabling for shorts or damage (measure resistance across resistor terminals).

Browse all codes in this manual (32)
Verified technical data. Last updated: April 2026