Omron · SXF Inverter
This fault signifies that the internal temperature of the VSD has exceeded its safe operating limits. This can result from insufficient cooling (e.g., blocked filters, fan failure), high ambient temperatures, or excessive motor load. Sustained high temperatures will degrade electronic components, potentially causing permanent damage or drive shutdown to protect itself from thermal stress.
Click steps to track your progress.
Clean or replace all cooling air filters on the VSD's intake and exhaust vents.
Verify VSD cooling fan operation by observing rotation and measuring fan motor voltage (e.g., 24VDC, 230VAC) at startup.
Measure the ambient temperature inside the VSD enclosure using a calibrated thermometer and ensure it is within specified limits.
Check for adequate clearance (e.g., 100mm top and bottom) around the VSD for proper airflow. Relocate equipment if necessary.
After disconnecting power, use compressed air to thoroughly clean dust and debris from the VSD heatsink and internal components.