A326.09

Pulse Output 2 Interrupt Feeding Error

Omron · SYSMAC CJ Series PLC

What does A326.09 mean?

This flag activates if the Pulse Value (PV) for pulse output 2 experiences an overflow or underflow while an interrupt input is received, or during the execution of the IFEED(892) instruction when a specified number of pulses is being moved and the origin is defined. This indicates a data integrity issue within the pulse counter, specifically during interrupt-driven feeding operations where the PV limits are exceeded.

Common Causes

  • PV overflow or underflow occurred during an interrupt input event while IFEED(892) instruction for pulse output 2 was active.
  • PV overflow or underflow occurred while the specified number of pulses was being moved by the IFEED(892) instruction for pulse output 2, with the origin defined.
  • The specified number of pulses in the IFEED(892) instruction for pulse output 2 was too large, causing the PV to exceed its 32-bit range.
  • Conflicting or poorly timed interrupt inputs while the IFEED(892) instruction for pulse output 2 is running.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Examine the ladder program logic related to the IFEED(892) instruction and associated interrupt inputs for pulse output 2.

  2. 2

    Confirm that the specified number of pulses for the IFEED(892) instruction for pulse output 2 will not cause the PV to exceed the 32-bit range.

  3. 3

    Analyze the timing of interrupt inputs relative to IFEED(892) execution for pulse output 2 to prevent concurrent actions leading to PV over/underflow.

  4. 4

    Stop and then restart the IFEED(892) instruction processing for pulse output 2 to clear the flag.

  5. 5

    Execute the INI(880) instruction for pulse output 2 to change (reset) its PV.

  6. 6

    Toggle the Pulse Output 2 Reset Bit A542.00 from OFF to ON to clear the PV for pulse output 2 (documented on page 183).