Omron · SYSMAC CJ Series PLC
This flag activates if the Pulse Value (PV) for pulse output 2 experiences an overflow or underflow while an interrupt input is received, or during the execution of the IFEED(892) instruction when a specified number of pulses is being moved and the origin is defined. This indicates a data integrity issue within the pulse counter, specifically during interrupt-driven feeding operations where the PV limits are exceeded.
Click steps to track your progress.
Examine the ladder program logic related to the IFEED(892) instruction and associated interrupt inputs for pulse output 2.
Confirm that the specified number of pulses for the IFEED(892) instruction for pulse output 2 will not cause the PV to exceed the 32-bit range.
Analyze the timing of interrupt inputs relative to IFEED(892) execution for pulse output 2 to prevent concurrent actions leading to PV over/underflow.
Stop and then restart the IFEED(892) instruction processing for pulse output 2 to clear the flag.
Execute the INI(880) instruction for pulse output 2 to change (reset) its PV.
Toggle the Pulse Output 2 Reset Bit A542.00 from OFF to ON to clear the PV for pulse output 2 (documented on page 183).