EL
ErrorLib
Brands
||
  1. Home
  2. Omron
  3. SYSMAC CJ Series PLC
  4. A327.09
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

A327.09

Pulse Output 3 Interrupt Feeding Error

Omron · SYSMAC CJ Series PLC

What does A327.09 mean?

This flag activates if the Pulse Value (PV) for pulse output 3 experiences an overflow or underflow while an interrupt input is received, or during the execution of the IFEED(892) instruction when a specified number of pulses is being moved and the origin is defined. This indicates a data integrity issue within the pulse counter, specifically during interrupt-driven feeding operations where the PV limits are exceeded.

Common Causes

  • PV overflow or underflow occurred during an interrupt input event while IFEED(892) instruction for pulse output 3 was active.
  • PV overflow or underflow occurred while the specified number of pulses was being moved by the IFEED(892) instruction for pulse output 3, with the origin defined.
  • The specified number of pulses in the IFEED(892) instruction for pulse output 3 was too large, causing the PV to exceed its 32-bit range.
  • Conflicting or poorly timed interrupt inputs while the IFEED(892) instruction for pulse output 3 is running.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Examine the ladder program logic related to the IFEED(892) instruction and associated interrupt inputs for pulse output 3.

  2. 2

    Confirm that the specified number of pulses for the IFEED(892) instruction for pulse output 3 will not cause the PV to exceed the 32-bit range.

  3. 3

    Analyze the timing of interrupt inputs relative to IFEED(892) execution for pulse output 3 to prevent concurrent actions leading to PV over/underflow.

  4. 4

    Stop and then restart the IFEED(892) instruction processing for pulse output 3 to clear the flag.

  5. 5

    Execute the INI(880) instruction for pulse output 3 to change (reset) its PV.

  6. 6

    Toggle the Pulse Output 3 Reset Bit A543.00 from OFF to ON to clear the PV for pulse output 3 (documented on page 183).

Browse all codes in this manual (20)
Verified technical data. Last updated: April 2026

Related Faults

0100CW Limit Stop Input Signal0101CCW Limit Stop Input Signal0200No Origin Proximity Input Signal
Source: Omron SYSMAC CJ Series PLC
Open Manual (Page 219)Search more codes in this manual