A445

Pulse Output 1 Stop Error Code

Omron · SYSMAC CJ Series PLC

What does A445 mean?

This word stores a specific error code if a fatal pulse output error occurs for pulse output 1. It also stores a code if pulse output 1 is stopped due to a limit input (CW or CCW) when the limit input function is set to be always enabled in the PLC Setup. The value stored in A445 provides specific information about the cause of the pulse output stop, requiring further interpretation.

Common Causes

  • A fatal pulse output error occurred during an origin search operation for pulse output 1.
  • Pulse output 1 stopped due to receiving an active CW or CCW limit input signal (A541.08 or A541.09) while the limit input function is enabled in the PLC Setup.
  • An internal malfunction within the pulse output module for pulse output 1 led to a stop.
  • Incorrect configuration of origin search parameters or limit switch logic for pulse output 1.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Read the specific error code value from auxiliary word A445 to diagnose the exact cause of the fatal error.

  2. 2

    If the error occurred during an origin search, verify the wiring and functionality of the origin sensor for pulse output 1.

  3. 3

    If stopped by a limit input, check the physical status and wiring of the Pulse Output 1 CW Limit Input Signal A541.08 and Pulse Output 1 CCW Limit Input Signal Flag A541.09.

  4. 4

    Verify the PLC Setup configuration for pulse output 1, specifically the setting for the limit input function (e.g., enabled/disabled as required).

  5. 5

    To clear the error code, initiate a new origin search for pulse output 1.

  6. 6

    Ensure that neither the Pulse Output 1 CW Limit Input Signal A541.08 nor the Pulse Output 1 CCW Limit Input Signal Flag A541.09 is active when attempting to clear the error.

Browse all codes in this manual (20)
Verified technical data. Last updated: April 2026

Related Faults

0100CW Limit Stop Input Signal0101CCW Limit Stop Input Signal0200No Origin Proximity Input Signal
Source: Omron SYSMAC CJ Series PLC
Open Manual (Page 219)Search more codes in this manual