EL
ErrorLib
Brands
||
  1. Home
  2. Omron
  3. SYSMAC CJ2 CPU Unit
  4. A402.03
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

A402.03

CPU Bus Unit Setting Error

Omron · SYSMAC CJ2 CPU Unit

What does A402.03 mean?

This fault indicates a setting error for a CPU Bus Unit. When an CPU Bus Unit Setting Error occurs, A402.03 and the bit in A427 corresponding to the Unit's unit number (0-F) are turned ON. The CPU Unit will continue operating, and the ERR/ALM indicator on the front of the CPU Unit will flash. These flags are refreshed when power is turned ON or I/O is recognized.

Common Causes

  • Incorrect configuration parameters or settings for a CPU Bus Unit.
  • Mismatched hardware or software settings for the CPU Bus Unit.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Identify the specific CPU Bus Unit with the setting error by checking bits A427.00 to A427.15.

  2. 2

    Compare the configured settings for the identified CPU Bus Unit in the CX-Programmer with the actual hardware.

  3. 3

    Reconfigure the CPU Bus Unit settings to match the expected parameters.

  4. 4

    Cycle power or re-recognize I/O to refresh the status after correcting settings.

Browse all codes in this manual (27)
Verified technical data. Last updated: April 2026

Related Faults

A10101Synchronous Input Data Refresh ErrorA259.12Task ErrorA295.09Indirect DM/EM Addressing Error
Source: Omron SYSMAC CJ2 CPU Unit
Open Manual (Page 628)Search more codes in this manual