A402.13

Duplicate Refresh Error

Omron · SYSMAC CJ2 CPU Unit

What does A402.13 mean?

This fault occurs when duplicated refreshing is performed for a Special I/O Unit. When the Duplicate Refresh Error Flag (A402.13) is ON, bit A426.15 indicates the cause of the error, and bits A426.00 to A426.11 contain the unit number (0-95) of the affected Special I/O Unit. The CPU Unit will continue operating, and the ERR/ALM indicator on the front of the CPU Unit will flash.

Common Causes

  • Configuration error leading to a Special I/O Unit's refresh being duplicated.
  • Incorrect I/O table or PLC Setup settings for a Special I/O Unit.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Identify the affected Special I/O Unit by reading the unit number from A426.00 to A426.11.

  2. 2

    Review the PLC I/O table and configuration settings for the identified Special I/O Unit.

  3. 3

    Ensure that the refreshing mechanism for the Special I/O Unit is configured uniquely.

  4. 4

    Clear the error flags (A402.13, A426.15) and the unit number bits (A426.00 to A426.11) after resolving the configuration issue.

Browse all codes in this manual (27)
Verified technical data. Last updated: April 2026