Omron · SYSMAC CJ2 CPU Unit
This flag turns ON when a CPU Bus Unit's unit number has been duplicated. Bits 00 to 15 correspond to unit numbers 0 to F. The Duplication Error Flag (A401.13) will also turn ON. The CPU Unit operation will stop, and the ERR/ALM indicator on the front of the CPU Unit will light.
Click steps to track your progress.
Identify the problematic CPU Bus Unit(s) by checking the ON status of A410.00 to A410.15 (Bits 00-15 for Unit numbers 0-F)
Physically inspect the DIP switch settings on all CPU Bus Units to verify unique unit numbers
Access the PLC Setup or I/O Table in CX-Programmer to review the configured unit numbers for all CPU Bus Units
Reconfigure either the physical DIP switches or the software settings to ensure each CPU Bus Unit has a unique unit number