Omron · SYSMAC CJ2 CPU Unit
This flag turns ON when a timeout error occurs during RS-232C communication. This indicates that a response from the connected device was not received within the expected timeframe after a transmission. This error is valid in Serial Gateway mode, NT Link mode, and for both Polling and Polled Units in Serial PLC Link Mode.
Click steps to track your progress.
Verify the connected device is powered ON and operating correctly
Inspect the RS-232C cable for continuity and proper connection at both ends
Check communication parameters, including device address and protocol settings, on both the PLC and the connected device
Adjust the communication timeout parameter in the PLC configuration if the connected device has a slower response time
Restart the RS-232C port by turning ON the Serial Port Restart Bit (A526.00) from OFF to ON