Otis · DSD 412 Elevator System
This fault signifies that the measured motor field current has exceeded 125% of the rated current, as defined by parameter #50. This condition can lead to motor field damage.
Click steps to track your progress.
Check the motor field winding for any signs of a partially shorted coil.
Review and verify the settings for parameters #49, #50, #51, #52, #54, and #55.
Verify that the wiring phasing for module A3 is correct.
Check and verify the current tap setting at A3, TB4, and the calibration switch A3 SW1 setting.
Inspect module A3 for any malfunction in the motor field power circuit.