401

EXCESSIVE FIELD CURRENT

Otis · DSD 412 Elevator System

What does 401 mean?

This fault signifies that the measured motor field current has exceeded 125% of the rated current, as defined by parameter #50. This condition can lead to motor field damage.

Common Causes

  • Partially shorted motor field coil, drawing excessive current.
  • Incorrect data entry in parameters #49, #50, #51, #52, #54, & #55, leading to an unstable motor field current regulator.
  • Mis-wiring of module A3, resulting in incorrect phasing.
  • Incorrect current tap selected at A3, TB4, or an improper A3 SW1 setting.
  • Malfunction within the motor field power circuit, possibly in module A3.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the motor field winding for any signs of a partially shorted coil.

  2. 2

    Review and verify the settings for parameters #49, #50, #51, #52, #54, and #55.

  3. 3

    Verify that the wiring phasing for module A3 is correct.

  4. 4

    Check and verify the current tap setting at A3, TB4, and the calibration switch A3 SW1 setting.

  5. 5

    Inspect module A3 for any malfunction in the motor field power circuit.