Otis · GAA21750AK3 Service Tool
This code indicates that one or more internal selftests of the LCB_II board's memory (EPROM, EEPROM, RAM) or the Remote Serial Link (RSL) did not complete successfully. A failed selftest can signify a hardware fault, leading to unreliable or non-operational system behavior for the GAA21750AK3 service tool.
Click steps to track your progress.
Run the selftest multiple times using the GAA21750AK3 service tool to confirm the failure is consistent.
Observe the flashing question mark on the display to identify which specific sub-test (PR EPROM, EE EEPROM, RA RAM, RS Remote Serial Link) is failing.
If the EEPROM test fails on its initial run with a new EEPROM, run it again after the first write operation.
Inspect RSL connections and the associated module if the RS test (Remote Serial Link) fails.
Check for correct memory addresses if configuring memory content, ensuring they are within valid RAM boundaries.