FAIL

Controller Runtime Failure

Phoenix Contact · AXC F 1050 Controller

What does FAIL mean?

This fault indicates a critical issue within the controller's IEC 61131 runtime system. It can either mean a runtime error has occurred in the application program or, more severely, the controller's hardware watchdog has been triggered, signifying a system lock-up or critical malfunction.

Common Causes

  • A runtime error has occurred within the IEC 61131 application program.
  • The controller's hardware watchdog has been triggered.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Connect to the controller with PC Worx Engineer and check the diagnostic logs for specific runtime error messages.

  2. 2

    Review the IEC 61131 application program for logical errors, array out-of-bounds access, or resource exhaustion.

  3. 3

    If the hardware watchdog is triggered, perform a power cycle on the controller.

  4. 4

    Isolate potentially problematic sections of the application program by disabling/enabling parts to pinpoint the cause of the watchdog trigger.

Browse all codes in this manual (9)