Phoenix Contact · ib il safe 2-eco
An error in the reset circuit has occurred: either the readback contact of an external actuator is open (external error), or an internal normally open (N/O) contact is welded shut (internal error). This state is present when sensor circuits 1 and 2 are active, the reset/start circuit is activated, and the segment circuit is open. This prevents the reset circuit from operating correctly, thereby compromising machine safety.
Click steps to track your progress.
For external errors: Check the external actuator for proper operation and verify the state of its readback contact
For internal errors: Perform a power down reset (switch off and then re-apply operating voltage)
After addressing the error and performing any power down reset, conduct a subsequent function test