Schindler · Altivar 212 Variable Frequency Drive
This fault is triggered when the [Auto Torque Boost] (F402) parameter is set too high or the motor impedance is too low, leading to excessive torque boost during operation or deceleration. It can also occur under specific deceleration conditions with Quadr. U/F control.
Click steps to track your progress.
Repeat the auto-tuning procedure for the motor.
Reduce the value of parameter [Auto Torque Boost] (F402).
Set parameter [Auto ramp] (AU1) to (0) [Disabled].
Decrease the deceleration ramp by adjusting parameter [Deceleration time 2] (F501) and [Commut. ramp freq.] (F505).