Schindler · Altivar 312 Drive
This fault indicates insufficient line supply voltage, a transient voltage dip, or a damaged precharge resistor. The drive trips if the line voltage drops below specific thresholds: 160V for ATV312 M2/M3 models, 300V for N4 models, and 430V for S6 models.
Click steps to track your progress.
Measure the incoming line voltage at the drive's input terminals and verify it meets the drive's specifications, considering the tripping thresholds (160V for M2/M3, 300V for N4, 430V for S6).
If the precharge resistor is damaged, the drive may need to be replaced.