Schindler · Easy Altivar ATV310 Drive
For the ATV310 drive, this fault is detected when one or more phases of the main line supply to the drive are lost or significantly unbalanced. This protection primarily operates when the drive is under load and can be triggered by blown fuses or incorrect supply configuration (e.g., a 3-phase drive on a single-phase supply).
Click steps to track your progress.
Check the power connection to the ATV310 drive and inspect all input fuses for continuity.
Verify that a 3-phase line supply is used if the drive model (ATV310) is a 3-phase unit.
Measure the incoming line voltages (phase-to-phase and phase-to-neutral, if applicable) to confirm they are balanced and within tolerance.
If acceptable for the application and after a thorough risk assessment, disable reporting of this fault type by setting Input Phase loss detection (parameter 606) to 00.