F019

Ground short-circuit

Schindler · Easy Altivar ATV310 Drive

What does F019 mean?

This ATV310 fault indicates a ground fault condition detected in the system, typically at the drive output or within the motor/cabling. This poses a safety risk and can lead to equipment damage if not promptly addressed.

Common Causes

  • Short-circuit or grounding at the drive output terminals or within the motor windings
  • Ground fault occurring while the drive is in run state
  • Significant current leakage to ground, especially when several motors are connected in parallel to one drive

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect the motor from the drive and verify the cables connecting the drive to the motor for short circuits (phase-to-phase or phase-to-ground).

  2. 2

    Test the motor insulation resistance using a megohmmeter (megger) to check for ground faults or inter-phase shorts.

  3. 3

    Adjust the switching frequency (parameter 315) to a lower value if transients are suspected to be contributing to the fault.

  4. 4

    Connect chokes in series with the motor if high current leakage to ground is observed or multiple motors are driven by the same VFD.