Schindler · Easy Altivar ATV310 Drive
For the ATV310 drive, this fault indicates that the motor or application is operating at a speed significantly higher than expected, exceeding the drive's configured limits, potentially more than 10% above the Top frequency (parameter 308). This can be caused by control instability, high inertia loads, or incorrect speed loop parameters.
Click steps to track your progress.
Check the motor operation and physical condition for any issues contributing to overspeed.
Adjust the Top frequency (parameter 308) if the motor is consistently operating more than 10% above its current setting, ensuring it matches application requirements.
Add a braking resistor to the drive, if not already present, to dissipate regenerative energy during deceleration and prevent overvoltage.
Check the sizing of the motor, drive, and load to ensure they are appropriate for the application's speed and inertia demands.
Review and re-tune the parameters of the speed loop (gain and stability) to ensure stable operation and prevent oscillations.