Schneider Electric · Altistart 22 Soft Starter
A fault has been detected with the soft starter's bypass contactor, indicating an issue with its operation or associated wiring. This prevents the soft starter from entering or maintaining bypass mode, which can lead to motor stoppage or inability to start.
Click steps to track your progress.
1. Measure voltage across bypass contactor coil terminals; verify it matches control voltage (e.g., 24VDC, 120VAC) when soft starter attempts bypass mode.
2. Check continuity of bypass contactor auxiliary contact (e.g., terminals 13-14) using a multimeter; verify state changes with contactor activation.
3. Inspect bypass contactor poles and arc chutes for signs of excessive arcing, burning, or mechanical damage.
4. Verify wiring integrity from the soft starter bypass control output (e.g., terminal R1-COM) to the bypass contactor coil.