EL
ErrorLib
Brands
||
  1. Home
  2. Schneider Electric
  3. Altistart 22 Soft Starter
  4. COME
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

COME

Communication Interruption (Keypad)

Schneider Electric · Altistart 22 Soft Starter

What does COME mean?

The communication link between the remote keypad and the soft starter has been interrupted. This message flashes after 20 retries within a 50 ms timeout, indicating a loss of connection.

Common Causes

  • Loose or disconnected ribbon cable/communication cable connecting the remote keypad to the soft starter's communication port.
  • Excessive electromagnetic interference (EMI) disrupting the communication signals between the keypad and soft starter.
  • Faulty remote keypad unit or soft starter's communication port hardware.
  • Incorrect keypad connection or usage of a non-compatible cable length or type.
  • Physical damage to the communication cable (e.g., crushing, cut, broken conductor).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Power down the soft starter, then carefully inspect and re-seat the communication cable connecting the keypad to the soft starter.

  2. 2

    2. Check the communication cable for any visible damage, cuts, or crushed sections and replace it with an identical, compatible cable if necessary.

  3. 3

    3. Ensure the communication cable is routed away from power cables or other sources of high electromagnetic interference (EMI).

  4. 4

    4. Test communication with a known good, compatible remote keypad to rule out a faulty keypad unit.

  5. 5

    5. Measure voltage levels on the communication lines (e.g., 5VDC, data lines) at both ends of the cable to check for signal integrity.

Browse all codes in this manual (32)
Verified technical data. Last updated: April 2026

Related Faults

1Modbus Function Not Recognized2Invalid Modbus Address3Invalid Modbus Value
Source: Schneider Electric Altistart 22 Soft Starter
View Official PDFSearch more codes in this manual