InF

Internal Detected Fault

Schneider Electric · Altistart 22 Soft Starter

What does InF mean?

An internal hardware or software error has occurred within the soft starter itself. This signifies a malfunction of the device's internal components or firmware.

Common Causes

  • Malfunction of an internal sensor (e.g., temperature sensor on a heatsink, current sensor on a phase leg).
  • Failure of an internal control board component (e.g., processor, memory chip, internal power supply module).
  • Corrupted firmware or bootloader due to electrical noise or an incomplete update.
  • Power supply instability within the soft starter's control electronics circuitry.
  • Failure of internal gate drive circuitry responsible for firing the SCRs (Silicon Controlled Rectifiers).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Cycle power to the soft starter; wait a full 30 seconds after shutdown before reapplying power for a complete reset.

  2. 2

    2. Check for loose internal connections, especially ribbon cables or power supply connectors, by gently reseating them.

  3. 3

    3. Verify that the incoming control power supply (e.g., 24VDC, 120VAC to L1/L2) is stable and within specified limits using a multimeter.

  4. 4

    4. Look for visible signs of damage on the control board (e.g., burnt components, bulging capacitors, discoloration).

  5. 5

    5. If safely accessible and documented, measure the internal DC bus voltage (e.g., between P+ and N-) to verify proper power conversion.

Browse all codes in this manual (32)
Verified technical data. Last updated: April 2026