Schneider Electric · Altistart 22 Soft Starter
The input line voltage supplied to the soft starter has exceeded the permissible limits. This condition can potentially damage the soft starter's power components and other connected equipment.
Click steps to track your progress.
1. Measure the incoming line voltage (L1-L2, L2-L3, L3-L1) at the soft starter's input terminals using a true RMS voltmeter; monitor for spikes over time.
2. Verify that the supply voltage consistently remains within the soft starter's specified operating voltage range (e.g., 380-480VAC).
3. Check power quality upstream of the soft starter for transients using a power quality analyzer if persistent voltage spikes are suspected.
4. Review soft starter parameters for any voltage monitoring thresholds (e.g., P6-01 (Overvoltage Trip Level)) and ensure they are appropriately set for the application.
5. Confirm that the installed soft starter is rated for the nominal input line voltage (e.g., 400V, 480V, 600V).