Schneider Electric · Altistart 22 Soft Starter
The soft starter has exceeded the maximum number of motor starts allowed within a defined time period ('SLG' period, as configured by the 'Snb' parameter). This protection mechanism prevents excessive thermal stress on the motor and soft starter from frequent starting attempts.
Click steps to track your progress.
1. Review the application's process requirements to determine if frequent motor starts are genuinely necessary for operation.
2. Adjust the 'Snb' (max starts per hour) and 'SLG' (start inhibit grace period) parameters to match application demands, considering motor and starter thermal limits.
3. Inspect the control logic (PLC/DCS program) for errors that could cause rapid cycling of the motor start command.
4. Monitor the RUN command signal at the soft starter's LIx input terminals for unintended rapid ON/OFF transitions using a voltmeter.
5. Verify the motor's load characteristics to ensure it isn't stalling or having difficulty reaching full speed, which can trigger restart attempts.