Schneider Electric · Altistart 22 Soft Starter
The motor's acceleration period exceeded the maximum allowed starting time ('tLS' parameter). This often indicates that the motor is struggling to accelerate, possibly due to excessive load, an undersized soft starter, or incorrect parameter settings.
Click steps to track your progress.
1. Measure the actual motor current during start-up to assess load and compare it to the motor's full load ampere (FLA) rating.
2. Disconnect the motor from the load (if safe and feasible) and test start to determine if the motor accelerates normally without load.
3. Review and adjust the soft starter's ramp-up time (ACC parameter) and starting current limit (CLI parameter) to optimize acceleration.
4. Verify the 'tLS' (maximum starting time) parameter is set appropriately for the application's required acceleration profile.
5. Inspect driven mechanical equipment (e.g., bearings, belts, couplings) for signs of binding or excessive friction.