Schneider Electric · Altistart 22 Soft Starter
The input line voltage supplied to the soft starter has dropped below the permissible operating limits or is entirely absent. This condition prevents proper operation and can lead to control issues or motor stoppage.
Click steps to track your progress.
1. Use a true-RMS voltmeter to measure the phase-to-phase voltages (L1-L2, L2-L3, L3-L1) at the soft starter's input terminals.
2. Check all upstream circuit breakers and fuses (including control circuit fuses if applicable) for tripped status or continuity.
3. Inspect all power connections at the soft starter's L1, L2, L3 terminals and the main incoming disconnect for tightness and corrosion.
4. Monitor the incoming supply voltage over a period using a power quality analyzer to detect intermittent sags or drops.
5. Review the soft starter's undervoltage trip threshold (e.g., USF parameter) to ensure it is set appropriately for the nominal supply voltage.