Schneider Electric · ALTIVAR 28 Variable Speed Drive
This fault occurs when the DC bus voltage within the drive controller is too high, either during steady-state operation or acceleration, usually caused by an excessively high incoming line voltage. High DC bus voltage can stress and damage the drive's internal capacitors and power semiconductors.
Click steps to track your progress.
1. Measure incoming AC line voltage (L1-L2, L2-L3, L3-L1 terminals) with a true RMS multimeter and compare to drive's rated input voltage.
2. Verify acceleration ramp time (Parameter P0-11) is not excessively short, which can cause voltage spikes.
3. Check input transformer taps if applicable and adjust to lower output voltage (if within acceptable range).
4. Monitor DC bus voltage (drive display parameter P0-08 or similar) during operation to observe peak voltage.
5. Consider installing an AC line reactor or surge protector to mitigate line voltage spikes.