This error occurs on the remote display terminal, indicating a communication timeout (50 ms) after 20 attempts to establish or maintain communication with the drive. This typically points to a faulty connection between the terminal and the drive, or incorrect communication settings, leading to a loss of display functionality and control.
Click steps to track your progress.
1. Inspect the communication cable connecting the remote display to the drive for any physical damage (cuts, pinches) or loose connections at both ends.
2. Verify that the remote display unit is correctly seated in its mounting slot or securely connected to the drive's communication port.
3. Check for strong sources of electromagnetic interference (EMI) near the communication cable; re-route the cable if necessary, ensuring proper shielding.
4. If configurable, verify that the communication address and baud rate settings on the remote display match those configured in the drive (e.g., P5-01, P5-02).
5. Attempt to connect a known-good, compatible remote display unit to the drive to determine if the issue is with the original display or the drive's communication port.