Schneider Electric · Altivar 312 Variable Frequency Drive
This fault indicates a problem with the drive's internal capacitor precharge circuit, typically related to the precharge relay control or a damaged precharge resistor. The precharge circuit is vital for safely charging the DC bus capacitors upon power-up. If unresolved, the drive cannot power up correctly and will remain inoperable.
Click steps to track your progress.
1. Disconnect input power (L1, L2, L3) and wait for the DC bus voltage (e.g., terminals DC+, DC-) to discharge safely to <50VDC.
2. Measure resistance of internal precharge resistors (requires drive disassembly and specific technical knowledge).
3. Test the precharge relay (if accessible) for coil continuity and contact operation using a multimeter.
4. Verify input line voltage (e.g., L1-L2, L2-L3, L3-L1) is stable and within specified limits during the power-up sequence.
5. Check for proper closure of the main input contactor (if external to the drive) after the precharge cycle.